FAQ

  1. Home >
  2. FAQ

Question: when the generator operation but without voltage is generated?
 
Solution:
 
1 Check voltmeter selector switch in the OFF position is it right?

 
2 Check the fuse, usually mounted on the generator terminal box (box)

 
3 additional voltage meter to measure AC motor terminal voltage, such as normal check generator to control line connection. Check voltage meter, such as necessary for a

 
4 check AVR and check the alternator rotating diode, “manual " to obtain more detailed information
 
5 diesel engine to convey speed is normal
 
Question : When the START signal input but not starting the engine, either manually or by remote control switch of automatic signal are not a car.
 Solution:

 
1 check all the emergency stop button is loosen (including remote control button) such as remote control parking, check whether it has connection terminals (remote parking).
 
2 check whether the “OFF control switch”

 
3 check the fault indicator light, if required, repair instructions after fault reset

 
4 check control screen battery voltage, such as voltage, check the fuse, such as low voltage on the battery charger for charging and try again another machine connection, attention in the demolition and connect the battery line, a control switch is in the OFF position
 
5 check in on the starting motor magnetic DC voltmeter is connected with the connector and the battery cathode, with manual control switch to the START tries to start, such as voltage starting motor or magnetic fault, will have to be replaced; if no voltage, check the control panel wiring is loose or short circuit
 
6 such as line nondestructive then for printed circuit board
 
Question : starting diesel engine fault , The engine to rotate but not the engine or a diesel engine starter for 20 seconds
 
Solution:
 
1 check the fuel level
 
2 examinations in the casing, emergency stop button is reset
 
3 check the fuel control magnetic suction connection whether there is voltage
 
4 examinations in AC generator side fuse
 
5 check the fuel pipe and filter is clogged
 
6 if in the exhaust system of white smoke fuel has entered the engine, but the engine car. Please check ( Engine Manual ) further examination
 
7 if the ambient temperature is low, such as a hot start, please use the
 
8 check engine oil pressure sensor plug
 
Question : LOW BATTERY VOLTAGE warning lamp on, low battery voltage alarm
 
Solution:
 
1 check the battery voltage 12 volts battery at least 12 V 24 V battery at least 24 volt generator
 
2 static when the battery voltage is low the cell detachment and use another charger charging or running diesel engine charging
 
3 if the battery voltage is low, but the power is in operation, which diesel driven charger is not charging, down to check the fan belt
 
4 such as fan belt is loose, then check the charging AC diesel powered charger reference manual ", " diesel engine
 
5 if the battery cannot charge, battery replacement
 
6 once the fault has been ruled out, press the reset button to clear the fault

 

Water-cooled Diesel Generator Purchasing Guide 
Dear Valued Customer
 If you need more details when you select the water-cooled diesel generator,we would like to guide you  get more necessary information:
1. Power request: Please make sure what the output power is for the generator.
 A. Power Output:
 ①.     KVA is different form KW,  1KVA=0.8KW
 ②.     Prime (Rated) power and Standby (Max) power:  Max power=1.1 X Rated power
 B.   Output of the Voltage & Frequency:
 ① Single phase or Three phase? 
 ②  50Hz or 60Hz?
2. Model request: 
 please provide more detailed request for the generator as possible as you can( such as color, model, any special request, etc), or visit more pages of our official website to get more contents. At the same time, we can also assist you to match the suitable model for you 
 

We have open type diesel generator and silent type diesel generator for choices as the pictures showed.

 

3.As for the engines for generator: 
 we can provide Cummins series ,Perkins Series ,Doosan series ,Volvo series ,Deutz series , Weichai series , Yangdong  series,   Yuchai series ,Shangchai series and FOTONG ISUZU series for your options. The rotate speed is 1500r/m or 1800r/m normally. The power of engine is usually 10% larger than generator’s power for figuration, because we should consider the mechanical loss when mechanical conversion.
 
4.As for the Alternators of Generator
 we usually configure Leroy-somer,Original Stamford ,and copy Stamford Alternator .
5. Control panel: 
  ①mechanical control panel as pictures
 

②Intelligent control panel, generator controller: Smartgen Genset auto control series ,Harsen Genset auto control series ,Deepsea Genset auto control series and china types, as pictures.

    

 
 

6. Protection device request
 We will fit the Air switch and “four protection” device when the rated output power exceeds 10KW on the normal condition.
7. Preheater request
 If you use the generator set in the extreme cold /frozen area, please make it clear.In this case, we can fit the preheater to start the set, otherwise, start the generator directly without protecting will cause it broken or damaged
 
8. About the oil tank
 The standard configuration of tank is 100L for it, if you have special requirement or no need tank, please remark.
10. The intelligent control (ATS).
 If the generator set used in government, hospital, telecom, Army, bank, etc or some Places where need Uninterruptible power supply, please make sure to configure the Automatic Transfer Switch(ATS) to achieve the automatic conversion between national normal electricity and the generator. To guarantee the regular power is off, we can start the standby generator in Momentary and Uninterruptedly supply the power
 
II ) The important notices of installation
 1. Please install it draughty place, generator side should be enough inlet hole position included, the engine end should be good outlet hole included as well
 
 2. Pleas keep clean in installment place and avoid the acid, alkaline or other corrosive gas. Please also include extinguishing unit
 3. If install it indoor, please fit the smoke-ejecting pipe to extend to outdoor.The channel bends are less(equal) three pcs to ensure to discharge smoke smoothly ,The output of the pipe should be lower than input to prevent rainwater immited
 
 4. The generator set should be installed in horizontal ground firmly, we should use the quakeproof pad or foot bolt between the set and ground
 5. The shell of set must be reliable protective earthing and lightning protection device.Strictly prohibit to use the grounding device of power grid directly to connect the diesel genset.
 
 6. The two-way switch should be extremely reliable between the regular power grid and the diesel genset
 
 7. The connecting wire of starter battery should be firmly

 

 